Chiller Module Specifications & Features
K-O Concepts Models MCR - DR        
MODEL NUMBERS MC-DR  
Cooling Capacities¹  Watts 100 200  
  BTU/hour 340 680  
Cooling Process Compressor All models use refrigerant based compressors.  
Refrigerant Type R134a All models use R134a (HFC-134a) / CFC-free.  
Heat Dissipation      
Note:  Air flows from front to back of cabinet. Air (air cooled) All models dissipate heat to ambient air via fan.   
Process Refrigerant Temperature Range °C / °F                                                                                    10-30° / 50-86°  
Process Refrigerant Temperature Stability² °C ±0.1°  
Ambient Air Temperature Range °C / °F         15-30° / 59-86°  
Process Refrigerant Transfer Lines 5/16 Inch O.D. Standard Feature:  3-12 feet  
Process Refrigerant Connections Rear-Panel Standard:  Hard Plumbed  
  Location Optional:  Quick Disconnect  
Cold Plate Configuration Catalog or custom cold plates installed.  
Note: Custom cold plate shown.      
Input Power Requirements / Selectable Volts AC AC Mains:  90-264 VAC / 1Ų / 50-60 Hz  
Dual Mains:  Universal AC or 24-28 VDC Volts DC DC Mains:  24 or 28 VDC
Optional Input Power Volts DC DC Mains:  24 or 28 VDC
Single Mains:  24 or 28 VDC    
Full Load Amperage (typical AC Mains) Amps @      
Note:  Typical line current @ 60 Hz. 117 / 230 VAC 1.0 / 0.5 1.4 / 0.7  
  Amps @      
  24 VDC 4.0 6.0  
Circuit Breaker SPST Lighted circuit breaker located on back panel.  
Weight Dry lbs. / kg. 9.0 - 11.5 / 4.1 -  5.2
Cabinet Dimensions (W x D x H) Width: in / mm 17.0 / 432  
Note: Standard 19 inch rack-mount configuration, fully enclosed, w/ 3.5 inch / 5 unit (U) high front panel. Depth: in / mm 8.0 / 203  
Height: in / mm 3.42 / 87
Panel: in / mm 19.0 W x 3.42 H / 482.6 W x 87 H  
Process Refrigerant Temperature Controller Digital (PID) controller w/ dual display.  
Condenser Fan Speed-controlled for quiet operation.  
Table-Top Model Optional Feature: For non-rack applications.  
Notes:
*     Cooling capacities require adequate cold plate and delta temperature between cold plate and heat load.
*     Temperature stability performance requires a stable heat load input.     
*     Data shown is with 30°C / 86°F (unrestricted) ambient air.
*     Specifications are subject to change without notice.   